Generator Stator Bar Abrasion Risk and Prevention

Generator Stator

Mechanical Dynamics & Analysis has analyzed and resolved generator stator bar abrasion events that have become common on some newer GE® Frame 7F and 324, 330, or 390 generators. The damage can cause ground faults leading to forced outages and complete stator rewinds. A principal cause of the abrasion is traceable to side ripple spring-induced […]